User Guide DLX Series L00410623-1 11
Turn OFF the DC switch.
DANGER
Always disconnect the PV array cables from the inverter after turning the AC and
DC OFF, but before removing the covers, as the PV array can supply up to 600 V
DC
to the inverter when exposed to sunlight.
Remove the four screws on the lower cover with a 4 mm hex key.
Take the cover off carefully.
Figure 2.4.5: Lower cover
Store the lower cover and screws safely to avoid loss or damage.
Fasten the screws on the lower cover with a torque of 1.0 Nm
CAUTION
Never remove the inverter lower cover in wet conditions! Removal of the inverter
lower cover during rain or in damp conditions can damage sensitive internal
electronic components.