Danfoss C67 Podręcznik Użytkownika Strona 12

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 84
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 11
Installation
10g
10.5 Indirectly connected heating system with
or without mixing loop and secondarily
connected storage tank
System settings
Circuit Line Description Recomm.
setting
I 17 Influence on desired flow temp. 3
I 43 Priority or parallel operation 99
I 51
DHW charging pump /
changeover valve
OFF
I 53
Desired flow temperature at
DHW charging
OFF
I 67
Adaptive function of S2 flow
temperature during DHW
charging
20
I 140
Function of temperature sensor
S5
2
I 152
Max limitation temperature at
sensor S2 during DHW charging
70*
* Line 152 = desired charging temperature
Heating circuit II can only be operated against heating circuit I.
This means that heating circuit II cannot be supplied if heating
circuit I is deactivated.
Przeglądanie stron 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 83 84

Komentarze do niniejszej Instrukcji

Brak uwag