VMIFB202
Alarm Brine
Action:
Check the set value on ALARM BRINE in the heat pump’s control computer under service-heat pump-temperatures-alarm brine.
Check that the brine sensor displays the correct value! See section sensor.
The alarm is triggered when the temperature on BRINE OUT is as low or lower than the set value on ALARM BRINE. In the factory setting
this function is inactive.
If the problem is caused by a faulty setting in the ALARM BRINE try adjusting the temperature down.
NOTE! Bear in mind that if one sets the alarm temperature lower than what the liquid in the Brine circuit is freeze protected against it
will result in low pressure alarm problems.
Troubleshooting Guide Alarm brine