31
Wiring
Digital Inputs
Multiple Starts from One command
Common connected, terminal 20, on each unit
Maximum of 200mV
In the example above, one switch is used to start multiple drives. The +24Vdc from the first
drive is being sent to the other drives. Notice that a wire most be connected between all the
Digital Input commons, terminal 20. There is a maximum of 200mV coming from the power
supply of the first drive, which limits the number of drives that may be started.