InstallationGuideECLComfort210/310,applicationA214/A314
Lowesttemp.
11150
CircuitSettingrange
Factorysetting
1
10...50°C30°C
Thealarmfunctionwillnotbeactivatedifthedesiredow/duct
temperatureislowerthanthesetvalue.


Alarmoverview,ingeneral
CircuitSettingrange
Factorysetting
1
Accesstooverviewshowingthealarmnumber/alarmtype.Thealarm
numberisenteredintothealarmregisterandcanbeobtainedfroma
SCADAsystem.
Example:"5:Temp.monitor":Ifanalarmisactivatedbecauseofconditions
in'Temp.monitor'thealarmnumber5isplacedinthealarmregister.












