Data sheet ECL Comfort 100M
Range Factory setting
Heating curve (H) 0.2 to 2.2 1.2
Parallel displacement +/-8 x H 0
Heating cut-out Off, 18 °C 18 °C
Reduced temperature 0 to 14 K or Auto Auto
Frost protection Fixed 10 °C
Max. flow limit 45, 90 °C 90 °C
Min. flow limit 10, 25 °C 10 °C
Neutral zone Fixed 3 K *)
Proportional band Fixed 80 K *)
Integration time Fixed 60 sec *)
Motorized valve constant 20 or 120 sec 120 sec
Supply voltage 230 V a.c. - 50 Hz
Voltage range 207 to 244 V a.c. (IEC 60038)
Power consumption 5 VA
Load on relay outputs 4(2) A - 230 V a.c.
Load on triac outputs 0.2 A - 230 V a.c.
Supply voltage 24 V a.c. - 50 Hz
Voltage range 21.6 to 26.4 V a.c. (IEC 60038)
Power consumption 5 VA
Load on relay outputs 4(2) A - 24 V a.c.
Load on triac outputs 1 A - 24 V a.c.
Ambient temperature 0 - 50 °C
Storage temperature -40 - +70 °C
Enclosure Wall or panel mounting
Sensor type Pt 1000 (1000 ohm at 0 °C)
Grade of enclosure IP 41 - DIN 40050
- marking
in accordance with the standards
EMC-Directive 89/336/EEC, 92/31/EEC, 93/68/EEC,
EN 50081-1 and EN 50082-1
Low Voltage Directive 73/23/EEC and 93/68/EEC
Wiring - 230 V a.c.
Wiring - 24 V a.c.
General data
Settings
*) Factory settings that cannot be changed by the user