The grey
side of the
ECL Card
Extended service
Service parameter(s) 78-83
32g
78 Desired temperature for anti-bacteria function
Circuit Setting range Factory setting
I OFF / 1 ... 100 °C OFF
Set the desired temperature for the anti-bacteria function. The
DHW will be charged daily or once a week at the set temperature
to protect against bacteria. The function is always active on
Mondays from 00:00 and the DHW is charged according to the
period set in line 80.
OFF: The anti-bacteria function is not active.
1 ... 100:
The anti-bacteria function is active at the
desired temperature.
80 Anti-bacteria function period
Circuit Setting range Factory setting
I 5 ... 250 min. 120 min.
Set the period for the anti-bacteria function. When the set time
expires, the anti-bacteria function is stopped.
5 ... 250:
The anti-bacteria function is active for the
set period.
The function is activated in line 78 by setting the desired anti-
bacteria temperature.
83 Daily / weekly anti-bacteria function
Circuit Setting range Factory setting
I ON / OFF ON
Choose whether the anti-bacteria function is to be active daily or
weekly.
ON: The anti-bacteria function is active once a
day (from 00:00).
OFF: The anti-bacteria function is active once a
week (Mondays from 00:00).