Danfoss FC 300 Interbus Instrukcje Operacyjne Strona 23

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 22
12 QUICK STOP ACTIVE SWITCH ON DISABLED
Event: - Quick stop has been completed or - “Disable-Voltage” command
Action: - Disable drive function
- The power section can be switched off
13 All states MALFUNCTION REACTION ACTIVE
Event: - Drive malfunction detected Action: - Trigger malfunction reaction depending on the fault
14 MALFUNCTION REACTION ACTIVE MALFUNCTION
Event: - Malfunction reaction concluded
Action: - Disable drive function
- The power section can be switched off
15 MALFUNCTION SWITCH ON DISABLED
Event: - “Malfunction-Reset” command
Condition: - Malfunction is no longer present
Action: - Malfunction reset is executed
FC 300 Interbus Operating Instructions 5. How to Control the FC 300
MG.33.H3.02 - VLT is a registered Danfoss trademark
23
5
Przeglądanie stron 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 44 45

Komentarze do niniejszej Instrukcji

Brak uwag