FC 300
Bit (Hex) Unit diag-
nose bit
Warning word (Par.
16-92)
Alarm no.
00000001 112 Brake check 28
00000002 113 Power card over temper-
ature
29
00000004 114 Earth fault 14
00000008 115 Control card over tem-
perature
65
00000010 116 Control word timeout 18
00000020 117 Over current 13
00000040 118 Torque limit 12
00000080 119 Motor thermistor over
temp.
11
00000100 104 Motor ETR over temper-
ature
10
00000200 105 Inverter overloaded 9
00000400 106 DC link under voltage 8
00000800 107 DC link over voltage 7
00001000 108 DC link voltage low 6
00002000 109 DC link voltage high 5
00004000 110 Mains phase loss 4
00008000 111 No motor 3
00010000 96 Live zero error 2
00020000 97 10 V low 1
00040000 98 Brake resistor power
limit
26
00080000 99 Brake resistor short cir-
cuit
25
00100000 100 Brake chopper fault 27
00200000 101 Speed limit 49
00400000 102 Fieldbus comm. fault 34
00800000 103 24 V supply fault 47
01000000 88 Mains failure 36
02000000 89 Current limit 59
04000000 90 Low temperature 66
08000000 91 Voltage limit 64
10000000 92 Encoder loss 61
20000000 93 Output frequency limit 62
40000000 94 Unused -
80000000 95 Warning word 2 (ext.
stat. word)
-
FC 300
Bit (Hex) Comm. option STW (Par. 16-94)
00000001 Ramping
00000002 AMA tuning
00000004 Start CW/CCW
00000008 Slow down
00000010 Catch up
00000020 Feedback high
00000040 Feedback low
00000080 Output current high
00000100 Output current low
00000200 Output frequency high
00000400 Output frequency low
00000800 Brake check OK
00001000 Braking max.
00002000 Braking
00004000 Out of speed range
00008000 OVC active
00010000 AC brake
00020000 KTY warm
00040000 Fans warm
00080000 Unused
00100000 Unused
00200000 Unused
00400000 Unused
00800000 Unused
01000000 Unused
02000000 Unused
04000000 Unused
08000000 Unused
10000000 Unused
20000000 Unused
40000000 Unused
80000000 Unused
8.1.1. Warning and Alarm Messages
There is a clear distinction between alarms and warnings. When there is an alarm, the frequency converter will enter a fault condition. After the cause
for the alarm has been cleared, the master will have to acknowledge the alarm message before the frequency converter can start operating again. A
warning, on the other hand, may come when a warning condition appears, then disappear when conditions return to normal, without interfering with the
process.
Warnings
Warnings within the frequency converter are represented by a single bit within a warning word. A warning word is always an active parameter. Bit status
FALSE [0] means no warning, while bit status TRUE [1] means warning. Any bit change in the warning word will be notified by a change of bit 7 in the
status word.
Alarms
Following an alarm message the frequency converter will enter Fault condition. Only after the fault has been alleviated and the master has acknowledged
the alarm message by setting bit 7 in the control word, will the frequency converter resume operation. Alarms within the frequency converter are
represented by a single bit within an alarm word. An alarm word is always an action parameter. Bit status FALSE [0] means no fault, while bit status
TRUE [1] means fault.
8. Troubleshooting FC 300 Interbus Operating Instructions
42
MG.33.H3.02 - VLT is a registered Danfoss trademark