Danfoss VLT 8000 AQUA Instrukcje Operacyjne Strona 110

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 210
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 109
VLT
®
8000 AQUA
References and Limits 200-228
In this parameter group, the frequency and reference
range of the frequency converter are established.
This parameter group also includes:
- Setting of ramp times
- Choice of four preset references
- Possibility of programming four bypass frequencies.
- Setting of maximum current to motor.
- Setting of warning limits for current, frequency,
reference and feedback.
201 Output frequency low limit, f
MIN
(MIN. FREQUE NC Y)
Value:
0.0 - f
MAX
0.0 HZ
Function:
This is where to select the minimum output frequency.
Description of choice:
A value from 0.0 Hz to the Output frequency high limit,
f
MAX
frequency set in parameter 202 can be selected.
202 Output frequency high limit, f
MAX
(MAX. FREQUENC Y)
Value:
f
MIN
- 120 Hz
(par. 200 Output frequency range)
60 Hz/
50 Hz
) Global factory setting different from North
American factory setting.)
Function:
In this parameter, a maximum output frequency
can be selected that corresponds to the highest
speed at which the motor can be.
NB!:
The output frequency of the frequency
converter can never assume a value higher
than 1/10 of the switching frequency
(parameter 407 Switching frequency).
Description of choice:
A value from f
MIN
to the choice made in parameter
200 Output frequency range can be selected.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.83.A2.02 - VLT is a registered Danfoss trademark
108
Przeglądanie stron 109
1 2 ... 105 106 107 108 109 110 111 112 113 114 115 ... 209 210

Komentarze do niniejszej Instrukcji

Brak uwag