VLT
®
8000 AQUA
Present output frequency
The value of the present output frequency of the
frequency converter at any given time is transmitted
as a 16-bit word. The value is transmitted in the form
of whole numbers 0 32767 (±200 %).
16384 (4000 Hex) corresponds to 100 %.
The output frequency has the following format:
0-16384 (4000 Hex)
0-100 % (Par. 201
Output frequency low limit - Par. 202 Output
frequency high limit).
E
xample - Status word and present output frequency:
The master receives a status message from the
frequency converter saying that the present output
frequency is 50 % of the output frequency range.
Par. 201 Output frequency low limit =0Hz
Par. 202 Output frequency high limit =50Hz
Status word = 0F03 Hex. Status
message
Output frequency = 2000 Hex. 50 % of the
frequency range,
corresponding to 25 Hz.
MG.83.A2.02 - VLT is a registered Danfoss trademark