Non UL compliance
If UL/cUL is not to be complied with, Danfoss recommends
using the fuses mentioned in the below table, which will
ensure compliance with IEC 61800-5-1:
In case of malfunction, not following the fuse recommen-
dation may result in damage to the frequency converter.
UL Non
UL
Bussmann Bussmann Bussmann Bussmann Max.
Fuse
Power
kW
Type RK5 Type RK1 Type J Type T Type
gG
3 x 200-240V
0.25 FRS-R-10 KTN-R10 JKS-10 JJN-10 10
0.37 FRS-R-10 KTN-R10 JKS-10 JJN-10 10
0.75 FRS-R-10 KTN-R10 JKS-10 JJN-10 10
1.5 FRS-R-10 KTN-R10 JKS-10 JJN-10 10
2.2 FRS-R-15 KTN-R15 JKS-15 JJN-15 16
3.7 FRS-R-25 KTN-R25 JKS-25 JJN-25 25
5.5 FRS-R-50 KTN-R50 JKS-50 JJN-50 50
7.5 FRS-R-50 KTN-R50 JKS-50 JJN-50 50
11 FRS-R-80 KTN-R80 JKS-80 JJN-80 65
3 x 380-480V
0.37 FRS-R-10 KTS-R10 JKS-10 JJS-10 10
0.75 FRS-R-10 KTS-R10 JKS-10 JJS-10 10
1.5 FRS-R-10 KTS-R10 JKS-10 JJS-10 10
2.2 FRS-R-15 KTS-R15 JKS-15 JJS-15 16
3 FRS-R-15 KTS-R15 JKS-15 JJS-15 16
4 FRS-R-15 KTS-R15 JKS-15 JJS-15 16
5.5 FRS-R-25 KTS-R25 JKS-25 JJS-25 25
7.5 FRS-R-25 KTS-R25 JKS-25 JJS-25 25
11 FRS-R-50 KTS-R50 JKS-50 JJS-50 50
15 FRS-R-50 KTS-R50 JKS-50 JJS-50 50
18.5 FRS-R-80 KTS-R80 JKS-80 JJS-80 65
22 FRS-R-80 KTS-R80 JKS-80 JJS-80 65
30 FRS-R-80 KTS-R80 JKS-R80 JJS-R80 80
37 FRS-R-100 KTS-R100 JKS-R100 JJS-R100 100
45 FRS-R-125 KTS-R125 JKS-R125 JJS-R125 125
55 FRS-R-150 KTS-R150 JKS-R150 JJS-R150 150
75 FRS-R-200 KTS-R200 JKS-R200 JJS-R200 200
90 FRS-R-250 KTS-R250 JKS-R250 JJS-R250 250
5.2.5 EMC-Correct Electrical Installation
General points to be observed to ensure EMC-correct
electrical installation.
Use only screened/armoured motor cables and
screened/armoured control cables.
Connect the screen to earth at both ends.
Avoid installation with twisted screen ends
(pigtails), since this ruins the screening effect at
high frequencies. Use the cable clamps provide-
dinstead.
It is important to ensure good electrical contact
from the installation plate through the installation
screws to the metal cabinet of the frequency
converter.
Use starwashers and galvanically conductive
installation plates.
Do not use unscreened/unarmoured motor cables
in the installation cabinets.
How to Install VLT HVAC Basic Drive Design Guide
MG.18.C2.02 - VLT
®
is a registered Danfoss trademark 51
5 5