Data sheet ECL Comfort 300 / 301
6
VD.7C.A9.02 © Danfoss 11/2008
DH-SMT/DK
Functions ECL Comfort 300 / 301 has a custom-designed
display with backlight for monitoring and
setting.
The controller can be used as master or slave in
systems with master/slave controllers.
A remote control or room panel can be
connected to the system device bus.
Optional modules can be inserted into the
controller for communication via LON, MODBUS,
RS-232, or M-Bus (heat meter / flow meter).
A relay module can be added to extend the
performance of outputs if they are used in the
selected application.
The Auto Tuning function for the automatic
setting of control parameters for instantaneous
DHW production is available with the ECL Card
C66.
However, Auto Tuning is only applicable with
valves that are approved for Auto Tuning, i.e.
the Danfoss types VB 2 and VM 2 with split
characteristic as well as logarithmic valves such
as VF and VFS.
Motor protection, which ensures stable control
and a long life of the motorized valve, is
available in ECL C Cards except C12, C14, C25
and C35.
General data
Ambient temperature 0 - 50 °C
Storage temperature -40 - + 70 °C
Mounting On wall, in panel or on DIN rail
Sensor type Pt 1000 (1000 ohm at 0 °C)
Grade of enclosure IP 41 - DIN 40050
- marking
in accordance with the standards
EMC-Directive 89/336/EEC, 92/31/EEC, 93/68/EEC,
EN 61000-6-3 and EN 61000-6-1
Low Voltage Directive 73/23/EEC and 93/68/EEC
Wiring - 230 V a.c.
Supply voltage 230 V a.c. - 50 Hz
Voltage range 207 to 244 V a.c. (IEC 60038)
Power consumption 5 VA
Load on relay outputs 4(2) A - 230 V a.c.
Load on triac outputs 0.2 A - 230 V a.c.