Danfoss C37 Podręcznik Użytkownika Strona 1

Przeglądaj online lub pobierz Podręcznik Użytkownika dla Termostaty Danfoss C37. Danfoss C37 User`s guide Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 78
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 0
C37
C37
VI.7C.E6.02
2005.09
VI.7C.E6.02
2005.09
www.danfoss.com
User's Guide
Installer's Guide
www.danfoss.com
ECL Comfort
Installer's Guide
ECL Comfort
User's Guide
*087R8070*
*VI7CE602*
*087R8070*
*VI7CE602*
Mixing controller with ON / OFF
controlled DHW charging
Przeglądanie stron 0
1 2 3 4 5 6 ... 77 78

Podsumowanie treści

Strona 1 - Installer's Guide 

C37C37VI.7C.E6.022005.09VI.7C.E6.022005.09www.danfoss.comUser's Guide Installer's Guide www.danfoss.comECL ComfortInstaller's GuideEC

Strona 2

InstallationFor easy access, you should mount the ECL Comfort controller near the system. Select one of the three following methods:• Mounting on a w

Strona 4

InstallationElectrical connections - 230 V a.c. - in general12a230 V a.c. connections - without safety thermostatOptionalP2 / M2*For the heating syste

Strona 5 - Before you start

InstallationTerminal Description Max. load1 (L) Supply voltage 230 V a.c.2 (N) Supply voltage 230 V a.c.3 M1 Actuator - open 0.2 A / 230 V a.c.4 M1Act

Strona 6 - Identifying the system type

InstallationConnecting the temperature sensors and the busTerminal Description Type (recomm.)15 and 16 System device bus*, connections for room panel*

Strona 7

InstallationIt is important that the sensors are mounted in the correct position in your system. The temperature sensor mentioned below are sensors us

Strona 8

Installation14cConnecting the room panel / remote controlThe ECA 60 / 61 / 62 / 63 is activated by the setting in line 10 (section 32). The ECA 60 / 6

Strona 9

Installation

Strona 10 - Mounting the ECL Comfort

InstallationHow to insert your ECL Card the first timeAfter the power has been switched on, open the lid on the front side of the controller.Place the

Strona 11

InstallationUnderstanding the ECL CardThe ECL Card contains factory settings for a standard system. If the actual system differs from the standard syst

Strona 12 - 230 V a.c. - in general

The shown diagram is a fundamental and simplified example and does not contain all components that are necessary in a system.If the system you are abou

Strona 13

The greyside of theECL CardBasic set-upGeneral principlesWhen the controller is connected and operating you can check and adjust all or some of the ba

Strona 14 - Connecting and placing the

The greyside of the ECL CardBasic set-upActual timeYear05012 2205A31Month, dayUse the shift button to switch between minutes, hours, years, months and

Strona 15

The greyside of theECL CardBasic set-upMonitoring temperatures and system units - line B 18Controlled unitsFlow temp.(S3)0360B3ON11ON2ONReturn temp.(S

Strona 16

The greyside of the ECL CardBasic set-upShift to manual mode.Controlled units0360B3ON11ON2ONController modeChoose the unit you want to control. The se

Strona 17

The greyside of theECL CardBasic set-up1 28C103ON1ON2ONSlopeDisplacementSlopeCircuit Setting range Factory settingI / (II) 0.2 ... 3.4 1.8 / (1.8)The

Strona 18 - Inserting the ECL Card

The greyside of the ECL CardBasic set-up20bParallel displacementCircuit Setting range Factory settingI / (II) -9 ... 9 K 0 / (0) KIf you want to adjus

Strona 19

The greyside of theECL CardBasic set-up81111ON2ON21 Limit for heating cut-outCircuit Setting range Factory settingI 10 ... 30 °C 20 °CSet the outdoor

Strona 20 - Basic set-up

The greyside of the ECL CardBasic set-upMin. flow temp.011ON209423ON2ONMax. flow temp.Setting range2 Flow temperature limits, min. and max.Circuit Sett

Strona 21 - Setting the time and date

The greyside of theECL CardBasic set-upRoom temperature influence -line 323aThis section is only relevant if you have installed a room sensor orECA 60

Strona 22 - Monitoring temperatures

The greyside of the ECL CardBasic set-up23bB: Reference room temperature controlUsed if your heating system is not equipped with radiatorthermostats a

Strona 23 - Manual control

Table of ContentsSections in the Installer’s GuideThe documentation for the ECL Comfort controller is composed of numbered sections. Only sections rel

Strona 24 - Setting the heat curve

The greyside of theECL CardBasic set-up4 Proportional band, XpCircuit Setting range Factory settingI / (II) 1 ... 250 K 80 / (80) KSet the proportion

Strona 25

The greyside of the ECL CardBasic set-up7 Neutral zone, NzCircuit Setting range Factory settingI / (II) 0 ... 9 K 3 / (3) KSet the neutral zone to a

Strona 26 - Heating cut-out

The greyside of theECL CardBasic set-upThe controller can control the DHW temperature with either one or two tank temperature sensor(s). The controlle

Strona 27 - Flow temperature limits

The greyside of the ECL CardBasic set-up27bOne sensor (S6) Temp.Cut-out difference - line 1Cut-in difference - line 2Cut-outTimeP2 / P3Charging temperat

Strona 28 - Room temperature influence

Control & overviewsIs the ECL Comfort controller ready for use?Make sure that the correct power supply is connected to terminals 1 (Live) and 2 (N

Strona 29

Control & overviewsAdapting the ECL Comfort controller to the systemTurn the ECL Card so that the grey side faces you and push , if necessary.Set

Strona 30 - Control parameters

Control & overviewsECL Card settings(circuit I)30aA Time and date Section 17B System information Sections 18 & 19C Heat curveSection 20Se

Strona 31

Control & overviewsECL Card settings(circuit II)30bA Time and date Section 17B System information Sections 18 & 19C Setting ranges Factory

Strona 32

Control & overviewsService parameters (10-199)31aCircuit I (Heating)Lines Setting ranges Factory settings Your settings10 Choice of room panel /

Strona 33

Control & overviews31bService parameters (10-199)Circuit I (Heating)Lines Setting ranges Factory settings Your settings147 Acceptable temperature

Strona 35

The greyside of theECL CardExtended serviceAdjusting the serviceparameters32In addition to the settings in line 1 to 7 on the grey side of the ECL Car

Strona 36 - Section 20

The greyside of the ECL CardExtended service32aService parameter(s) 10-1110 Choice of room panel / remote controlCircuit Setting range Factory settin

Strona 37

The greyside of theECL CardExtended service32bService parameter(s) 12-13 12 BoostCircuit Setting range Factory setting(I) / (II) 0 ... 99% (0) / (0)%

Strona 38 - Service parameters (10-199)

The greyside of the ECL CardExtended serviceService parameter(s) 14-1532c14 Optimizing time constantCircuit Setting range Factory setting(I) / (II) O

Strona 39

The greyside of theECL CardExtended service32dService parameter(s) 16-1716 Frost protection by DHW circulation pumpCircuit Setting range Factory sett

Strona 40 - Adjusting the service

The greyside of the ECL CardExtended serviceService parameter(s) 20-2132e20 Optimization based on room / outdoor temperatureCircuitSetting range Fact

Strona 41 - ECL Card

The greyside of theECL CardExtended service32fService parameter(s) 22-2423 Valve exerciseCircuit Setting range Factory settingI / (II) ON / OFF OFF /

Strona 42 - Service parameter(s) 12-13

The greyside of the ECL CardExtended service31-34 Return temperature limitation The return temperature limitation is based on the outdoor temperature

Strona 43 - Service parameter(s) 14-15

The greyside of theECL CardExtended service31 Return temperature limitation - upper limit (X-axis) Circuit Setting range Factory setting(I) / (II) -6

Strona 44 - flow.ref(II)

The greyside of the ECL CardExtended serviceService parameter(s) 3532i35 Return temperature influence - max. limitationCircuit Setting range Factory s

Strona 45 - Service parameter(s) 20-21

VI.7C.E6.02Card C372005.09Sketch your applicationThe ECL Comfort controller series is designed for a wide range of heating, hot-water and cooling syst

Strona 46 - Service parameter(s) 22-24

The greyside of theECL CardExtended serviceService parameter(s) 3632j36 Return temperature influence - min. limitationCircuit Setting range Factory se

Strona 47 - -15 0 +15

The greyside of the ECL CardExtended service32kService parameter(s) 37-4137 Time constant for return temperature limitationCircuit Setting range Fact

Strona 48 - Service parameter(s) 31-34

The greyside of theECL CardExtended service32lService parameter(s) 4343 Priority or parallel operation Circuit Setting range Factory settingI OFF / 1

Strona 49 - Service parameter(s) 35

The greyside of the ECL CardExtended serviceService parameter(s) 44-5132m44 Max. DHW charging timeCircuit Setting range Factory settingII OFF / 1 ...

Strona 50 - Service parameter(s) 36

The greyside of theECL CardExtended serviceService parameter(s) 52-5532n52 Closed valve / normal operation Circuit Setting range Factory setting(I) /

Strona 51 - Service parameter(s) 37-41

The greyside of the ECL CardExtended service32oService parameter(s) 78-9078 Desired temperature for anti-bacteria functionCircuit Setting range Facto

Strona 52 - flow.ref II

The greyside of theECL CardExtended service32pService parameter(s) 141141 Override input selectionCircuit Setting range Factory setting(I) / (II) OFF

Strona 53 - Service parameter(s) 44-51

The greyside of the ECL CardExtended service32qService parameter(s) 147147 Acceptable temperature deviation below desired flow temperature (ΔT1ALARM)

Strona 54 - Service parameter(s) 52-55

The greyside of theECL CardExtended service32rService parameter(s) 148148 Acceptable temperature deviation above the desired flow temperature (ΔT2ALAR

Strona 55 - Service parameter(s) 78-90

The greyside of the ECL CardExtended service32sService parameter(s) 149149 Time interval ΔtALARM before activation of alarm functionCircuit Setting ra

Strona 56 - Service parameter(s) 141

InstallationThe ECL Comfort controller is a universal controller that can be used for various systems. Based on the shown standard systems, it is poss

Strona 57

The greyside of theECL CardExtended service196 Service pin - LONCircuit Setting range Factory settingI ON / OFF OFFThis setting is only used in connec

Strona 58

The greyside of the ECL CardExtended service32uService parameter(s) 199199 Master / slave addressCircuit Setting range Factory settingI 0 ... 9, 15 15

Strona 59 - 1 ... 99: Time interval Δt

The yellow side of theECL CardMiscellaneous34aCopying with the ECL CardCheck the ECL Card and the software generations (see following example).Insert

Strona 60 - Service parameter(s) 174-198

The yellowside of the ECL CardMiscellaneousCopy personal settings to additional controller(s) in identical systemsEnsure that the other controller(s)

Strona 61 - Service parameter(s) 199

7aDefinitionsAir duct temperatureTemperature measured in the air duct where the temperature is to be controlled.Balance temperatureThis setpoint is the

Strona 62 - Copying with the ECL Card

7bHumidity, relativeThis value (stated in %) refers to the indoor moisture content compared to the max. moisture content. The relative humidity is mea

Strona 63

The time shown in the display is one hour off?See the summer time changeover in line 198, section 32.The time shown in the display is not correct?The i

Strona 64 - Definitions

How to make an extra comfort period in the schedule?You can make an additional comfort period by pushing the shift and + buttons simultaneously for 2

Strona 65

The yellow side of theECL CardSave your personal settings to the ECL CardGo to line 9 (is not displayed), which is the second line below line 7.CardCC

Strona 66 - Hot points

The yellowside of the ECL CardRestore ECL Card dataAfter establishing your favorite temperatures, comfortperiods etc., and after copying these to the

Strona 67

Installation10.2 Indirectly connected system and secondarily connected DHW storage charging system (DHW priority)System settingsCircuit Line Descripti

Strona 68 - Advantages of the

The yellow side of theECL CardMonitor the current schedulesSelect between lines 1-7 (Monday, Tuesday ... Sunday) to see your individual schedules.L

Strona 69 - Restore ECL Card data

The yellowside of the ECL Card4bAdd an extra comfort periodPush the shift and + button simultaneously for 2 seconds.The new period appearsAdjust the n

Strona 70 - Set your personal schedule

The yellow side of theECL CardDuring scheduled operation (clock), the state indicator (a white arrow) will show you the control mode of the selected c

Strona 71 - Remove a comfort period

The yellowside of the ECL CardSet your room and DHW charging temperature3Go to display C.Circuit I:Setting the desired room temperature02Desired room

Strona 72 - Select circuit mode

The yellow side of theECL Card1aChoose your favorite display(circuit I)Choose the display - A, B, or C - for daily operations.Room temperature - displ

Strona 73 - Set your room and DHW

The yellowside of the ECL CardChoose the display - A, B, or C - for daily operations.DHW temperature - display ALineCircuitUpper tank temp. (S6)07A52D

Strona 74 - (circuit I)

The yellow side of theECL CardSchedule,DHW circulation pump (P3)1cChoose the schedule of the circulation pump by pushing the button until there is no

Strona 75 - (circuit II)

Save energy - save money - improve your comfort temperatureThe ECL Comfort controller is designed by Danfoss for the automatic temperature control of

Strona 76 - DHW circulation pump (P3)

Table of ContentsDaily useSection1 Choose your favorite display2 Select circuit mode3 Set your room and DHW charging temperature4 Set your personal sc

Strona 77

Installation10.4 Indirectly connected system and secondarily connected DHW storage tank with built-in heating coil (DHW priority)System settingsCircui

Strona 78

InstallationThe following heating systems are only applicable with relay module ECA 8010.6 Indirectly connected system and secondarily connected DHW s

Komentarze do niniejszej Instrukcji

Brak uwag