The grey
side of the
ECL Card
Basic set-up
8
1
1
1
1
ON
2
ON
2
1 Limit for heating cut-out
Circuit Setting range Factory setting
I 10 ... 30 °C 20 °C
Set the outdoor temperature limit at which you
want the heating system to stop.
The valve closes and after about 3 min. the heating
circulation pump stops.
The min. limitation set in line 2 will be ignored.
18 °C
Temp.
Actual Accumulated
outdoor temp. outdoor temp.
Heating OFF
Time
Heating Heating
This function can save energy by stopping the heating system
when the outdoor temperature gets above a set limit. The heating
system switches ON again when the outdoor temperature and
the accumulated outdoor temperature become lower than the set
limit.
The heating cut-out is only active when the controller mode is
scheduled operation. When the limit value is set to 30, there is no
heating cut-out.
Heating cut-out -
line 1
21