  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 84
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 17
18
Proportional Controllers for heating •
circuits
Can be used with RA-N, RA-G and •
RA-C
FEV-IF can be used in floor, ceiling or •
radiator heating
FEV-FF can be used with fancoil or •
induction units
The FEV is a proportional controller
which opens or closes the heating
valve as a function of the temperature
deviation.
FEV sensors can be applied in
combination with RA-N RA-G or RA-C
valves. The FEV sensors are equipped
with a direct acting valve-controller that
opens the valve when the temperature
drops below the set temperature. If the
set temperature is equal to or higher
than the room temperature the valve
is closed.
FEV-IF
To be applied in systems with
ceiling, floor or radiator heating. The
temperature adjuster/sensor should be
mounted on an internal wall at a height
of approximately 1.5 metres in such a
way that the room temperature can be
measured accurately.
FEV-FF
To be applied in systems with fancoils or
induction units. By placing the remote
sensor in the room-air inlet of the unit
a smaller response time to temperature
changes can be achieved which will
result in a more accurate temperature
control.
Type Code No. Sensor Capillary Tube Setting Range
FEV-IF 013G546700 Integrated Sensor 5 metres
17-27°C
FEV-FF 013G546600 Remote Sensor 2 + 2 metres
FEV-FF with remote sensor
FEV-IF with integrated sensor
Proportional Controller for Heating Circuits
FEV-IF and FEV-FF
Application
Floor, ceiling or radiator heating
Fancoils/induction units
Heating Circuit
Heating Circuit
RA-C
RA-N
RA-G
RA-C
RA-N
RA-G
FEV-IF FEV-FF
1. Heating adapter
2. Actuator
3. Adjustment bellows
4. Capillary reel
5. Remote temperature adjuster
6. Bellows
7. Remote temperature sensor (FEV-FF)