Danfoss REP24CO3 Dokumentacja Strona 61

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 84
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 60
61
Fully automatic control of •
disinfection
Easy to read LCD display•
Temperature register and log (SD •
Card)
Saves energy by shortening •
disinfection time of whole system
Reduction of limescale and •
associated costs
BMSconnectionpossible•
Alarm function•
The CCR2 system is used in conjunction
with MTCV valves to provide fully
automatic, optimised disinfection
and/or temperature logging for large
hot water systems. By optimising this
process electronically, energy savings
can be made by reducing the overall
disinfection time, and disinfecting
systems riser by riser.
Fully adjustable temperature logging is
available using standard Secure Digital
memory cards (SD). A 512mb SD card,
when fitted to the CCR2 (set to log temps
every 1 minute) will store over 2,000,000
records, or just over 1.5 years of data.
Recording intervals are programmable
and data can be read on any PC as data
files are saved in a common *.txt format
for easy integration into Excel or other
spreadsheet software.
One CCR2 can control 16 risers, this can
be expanded over a larger system by
connecting other units up in serial or
parallel.
Additional functions of the CCR2:
• Indicationofalarmstate
• Pumpprotectionfunction
• Visual indication of the progress of
disinfection process.
Type Designation Supply Voltage Actuator type Code No.
CCR2 Control
Disinfection Process Control and
temperature registration
24 Vac NC/16 003Z385000
Accessory
Type Designation Voltage Comments Code No.
TWA-A Thermal actuators 24 Vac 008H311000
TWA-A/ESMB
Thermal actuators with temperature
sensors ESMB
24 Vac 003Z104300
Adapter Adapter for TWA-A actuators for MTCV
For valve
DN15/DN20
003Z102200
ESMB Universal temperature sensor, PT1000 With 2.5m cable 087B118400
ESMB + pocket Universal temperature sensor, PT1000 With 2.5m cable 003Z104500
ESMC Surface Sensor, PT1000 With 2m cable 087N001100
Scheme for disinfection and registration temperature
Scheme for temperature logging
A - independent system (only sensor SO needed)
B - dependent system (sensor SO and connection to weather or another control needed)
CCR2
Disinfection Process Control & Temperature Logging