
VLT® 8000 AQUA
Installation
The total current consumption of the motors
is not to exceed the maximum rated output
current I
VLT,N
for the AFD.
Problems may arise at the start and at low rpm values if
the motor sizes are widely different. This is because the
relatively high ohmic resistance in small motors calls for
a higher voltage at the start and at low rpm values.
In systems with motors connected in parallel, the
electronic thermal relay (ETR) of the AFD cannot
be used as motor protection for the individual
motor. Consequently, additional motor protection
is required, such as thermistors in ground motor
(or individual thermal relays).
NOTE
Parameter 107 Automatic Motor Adaptation,
AMA and Automatic Energy Optimization, AEO
in parameter 101 Torque characteristics cannot
be used motors are connected in parallel.
■ Motor cables
See Technical data for correct sizing of motor
cable cross-section and length.
Always comply with national and local regulations
on cable cross-sections.
NOTE
If an unshielded cable is used, some
EMC requirements are not complied with,
see EMC test results.
If the EMC specifications regarding emission are
to be complied with, the motor cable must be
shielded, unless otherwise stated for the RFI filter
in question. It is important to keep the motor cable
as short as possible so as to reduce the noise level
and leakage currents to a minimum.
The motor cable shield must be connected to the
metal cabinet of the AFD and to the metal cabinet of
the motor. The shield connections are to be made
with the biggest possible surface (cable clamp).
This is enabled by different installation devices in
the different AFDs. Mounting with twisted shield
ends (pigtails) is to be avoided, since these spoil
the shielding effect at higher frequencies.
If it is necessary to break the shield to install a
motor isolator or motor contactor, the shield must be
continued at the lowest possible HF impedance.
MG.80.A6.22 - VLT is a registered Danfoss trademark
71
Komentarze do niniejszej Instrukcji