VLT® 8000 AQUA
Installation
■ Installation of VLT 8450-8600 380-480 V Compact IP
00/Chassis, IP 20/NEMA 1 and IP 54/NEMA 12
Cooling Side-by-side
All units in the above-mentioned series require a
minimum space of 400 mm (15.8 in) above the
enclosure and must be installed on a plane floor. This
applies to both IP 00/Chassis, IP 20/NEMA 1 and IP
54/NEMA 12 units.
Gaining access to VLT 8450-8600 requires
a
minimum space of 605 mm (23.8 in) in front of the
AFD.
All IP 00/Chassis, IP 20/NEMA 1 and IP 54/NEMA 12
units in the above-mentioned series can be installed
side by side without any space between them, since
these units do not require cooling on the sides.
■ IP 00 VLT 8450-8600 380-480 V
The IP 00/Chassis unit is designed for installation in a
cabinet when installed according to the instructions
in the Installation Guide MG.56.AX.YY. Please note,
that the same conditions as for NEMA 1/ IP20
and IP54/NEMA 12 must be fulfilled.