61 Termination of serial communication.
See Earthing/Grounding of shielded
(armoured control cables.
This terminal is not normally to be
used.
68, 69 RS 485 interface, serial
communication. When multiple
AFDs are connected to a
communication bus, switches
2 and 3 on control card in the
first and last units must be closed
(position ON). For the remaining
AFDs, switches 2 and 3 must be
open (OFF). The factory setting is
closed (position ON).
Switches 1-4
The dipswitch is located on the control card. It is used
for serial communication and external DC supply.
The switching position shown is the factory setting.
Switch 1 has no function.
Switches 2 and 3 are used for terminating an RS
485 interface, serial communication. In the first and
the last AFD, switches 2 and 3 must be ON. In the
other AFD, switches 2 and 3 must be OFF.
Switch 4 is used if an external 24 V DC supply is required
for the control terminals. Switch 4 separates the
common potential for the internal 24 V DC supply from
the common potential of the external 24 V DC supply.
NOTE
Please note that when Switch 4 is in position
"OFF", the external 24 V DC supply is
galvanically isolated from the AFD.
MG.80.A6.22 - VLT is a registered Danfoss trademark