User Guide DLX Series L00410623-1 27
Negative Grounded PV String
Figure 4.3.10: Negative grounded PV string
• The inverter is delivered from the
factory in an ungrounded PV string
configuration as standard.
• Connect the grounding strap between
N5 (fig. 4.3.9) and the DC ground
receptacle labeled GND/PE in the
inverter lower compartment.
Positive Grounded PV String
Figure 4.3.11: Positive grounded PV string
• Connect the positive conductors (+)
to the terminals labeled 2.Grounded,
and the negative conductors (-) to
the terminals labeled 1.Ungrounded.
• Switch the conductors connected to
N4 and P4 (fig. 4.3.9).
• Connect the grounding strap between
N5 (fig. 4.3.9) and the DC ground
receptacle labeled GND/PE in inverter
lower compartment.
4.3.4.4. Connection Procedures
• The DC conductors connecting the PV array to the inverter must each have a minimum
rating of 600 V
DC
at any operating temperatures.
• The DC conductor cables must be sized for correct temperature rating and sunlight
resistance. Use copper wire with a cross-section area of between 6 mm
2
to16 mm
2
/ 10
AWG to 6 AWG and temperature rating 90° C /194° F for all connections. Ensure
compliance with the relevant national electrical regulations!