34 User Guide DLX Series L00410623-1
Table 4.3: Position of the jumper for the termination resistance
Network connection
J
umper Position Pins
1. CAN termination resistance
2. RS-485 termination resistance
The pins are terminated.
The pins are disconnected.
4.3.7. Checks before Start Up
Mounting:
- Check that the bracket and the inverter are correctly mounted and secured.
PV wiring:
- Check that the PV cables are rated for the PV current and for the expected
environmental conditions.
- Check that the wiring is performed according to local and national electrical
regulations.
Connection:
- Check that the PV conductors are correctly torqued to the DC terminals.
- Check that all connectors and cable glands are correctly tightened and sealed.
DC side:
- Verify that the PV open-circuit voltage, V
OC
, does not exceed 600 V
DC
- Check that the DC polarity is correct.
AC side:
- Verify that the AC conductors on are correctly connected to the AC terminals.
Grounded conductors:
- Check that the grounded conductors are properly sized, and not fused or switched.
Jumpers:
- Check that the jumpers for the grounding setup and for the termination resistance
are correctly positioned according to the grounding setup.
Disconnects:
- Ensure that all current-carrying conductors on both the DC and AC side can be
disconnected, and that the disconnects are located correctly and are readily
accessible.
Overcurrent protection:
- Ensure that the overcurrent protection on both the DC and the AC side are rated
correctly, and capable of being changed without touching live contacts.
Inverter cover:
- Ensure that no cables interfere with the sealing of the inverter lower cover, and
fasten the cover firmly to the housing. Recommended tightening torque is 1.0 Nm
/ 0.74 ft-lbf.