3.1.3 0-3* LCP Custom Readout
It is possible to customize the display elements for various
purposes: *Custom Readout. Value proportional to speed
(Linear, squared or cubed depending on unit selected in
0-30 Custom Readout Unit) *Display Text. Text string stored in
a parameter.
Custom Readout
The calculated value to be displayed is based on settings in
0-30 Custom Readout Unit, 0-31 Custom Readout Min Value
(linear only), 0-32 Custom Readout Max Value, 4-14 Motor
Speed High Limit [Hz] and actual speed.
0
Custom Readout (Value)
P 16-09
Custom Readout
Unit P 0-30
Max value
P 0-32
Min value
Liniar
units only
P 0-31
Motor Speed
130BB779.10
Motor Speed
High limit
P 4-14 (Hz)
Linear Unit (e.g. Speed and ow)
Quadratic Unit (Pressure)
Cubic Unit (Power)
The relation will depend on the type of unit selected in
0-30 Custom Readout Unit:
Unit Type
Speed Relation
Dimensionless Linear
Speed
Flow, volume
Flow, mass
Velocity
Length
Temperature
Pressure Quadratic
Power Cubic
0-30 Custom Readout Unit
Option: Function:
Program a value to be shown in the display
of the LCP. The value has a linear, squared
or cubed relation to speed. This relation
depends on the unit selected (see table
above). The actual calculated value can be
read in 16-09 Custom Readout.
[0] None
[1] * %
0-30 Custom Readout Unit
Option: Function:
[5] PPM
[10] l/Min
[11] RPM
[12] Pulse/s
[20] l/s
[21] l/min
[22] l/h
[23] m3/s
[24] m3/min
[25] m3/h
[30] kg/s
[31] kg/min
[32] kg/h
[33] t/min
[34] t/h
[40] m/s
[41] m/min
[45] m
[60] Degree Celsius
[70] mbar
[71] bar
[72] Pa
[73] kPa
[74] m Wg
[80] kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[127] ft3/h
[140] ft/s
[141] ft/min
[160] Degree Fahr
[170] psi
[171] lb/in2
[172] in WG
[173] ft WG
[180] hp
0-31 Custom Readout Min Value
Range: Function:
0.0 CustomRea-
doutUnit*
[0.0 - 999999.99
CustomRea-
doutUnit]
This parameter allows the
choice of the min. value of the
custom defined readout
(occurs at zero speed). It is only
possible to select a value
different to 0 when selecting a
linear unit in 0-30 Custom
Readout Unit. For Quadratic
and Cubic units the minimum
value will be 0.
Parameters VLT HVAC Basic Drive Programming Guide