5.1.8 6-** Analog In/Out
Par.
No. #
Parameter description Default value 2-set-up Change
during
operation
Conver-
sion index
Type
6-0* Analog I/O Mode
6-00 Live Zero Timeout Time 10.0 s All set-ups TRUE 0 uint_8
6-01 Live Zero Timeout Function [0] Off All set-ups TRUE - Uint8
6-1* Analog Input 53
6-10 Terminal 53 Low Voltage 0.07 V All set-ups TRUE -2 uint_16
6-11 Terminal 53 High Voltage 10.0 V All set-ups TRUE -2 uint_16
6-12 Terminal 53 Low Current 4.0 mA All set-ups TRUE -2 uint_16
6-13 Terminal 53 High Current 20.0 mA All set-ups TRUE -2 uint_16
6-14 Terminal 53 Low Ref./Feedb. Value 0.0 N/A All set-ups TRUE -3 Int32
6-15 Terminal 53 High Ref./Feedb. Value 50.0 N/A All set-ups TRUE -3 Int32
6-16 Terminal 53 Filter Time Constant 0.01 s All set-ups TRUE -2 uint_16
6-19 Terminal 53 mode [1] Voltage mode 1 set-up TRUE - Uint8
6-2* Analog Input 54
6-20 Terminal 54 Low Voltage 0.07 V All set-ups TRUE -2 uint_16
6-21 Terminal 54 High Voltage 10.0 V All set-ups TRUE -2 uint_16
6-22 Terminal 54 Low Current 4.0 mA All set-ups TRUE -2 uint_16
6-23 Terminal 54 High Current 20.0 mA All set-ups TRUE -2 uint_16
6-24 Terminal 54 Low Ref./Feedb. Value 0.0 N/A All set-ups TRUE -3 Int32
6-25 Terminal 54 High Ref./Feedb. Value 50.0 N/A All set-ups TRUE -3 Int32
6-26 Terminal 54 Filter Time Constant 0.01 s All set-ups TRUE -2 uint_16
6-29 Terminal 54 mode [1] Voltage mode 1 set-up TRUE - Uint8
6-7* Analog/Digital Output 45
6-70 Terminal 45 Mode [0] 0-20 mA All set-ups TRUE - Uint8
6-71 Terminal 45 Analog Output [0] No operation All set-ups TRUE - Uint8
6-72 Terminal 45 Digital Output [0] No operation All set-ups TRUE - Uint8
6-73 Terminal 45 Output Min Scale 0.0 % All set-ups TRUE -2 uint_16
6-74 Terminal 45 Output Max Scale 100.0 % All set-ups TRUE -2 uint_16
6-76 Terminal 45 Output Bus Control 0.0 % All set-ups TRUE -2 uint_16
6-9* Analog/Digital Output 42
6-90 Terminal 42 Mode [0] 0-20 mA All set-ups TRUE - Uint8
6-91 Terminal 42 Analog Output [0] No operation All set-ups TRUE - Uint8
6-92 Terminal 42 Digital Output [0] No operation All set-ups TRUE - Uint8
6-93 Terminal 42 Output Min Scale 0.0 % All set-ups TRUE -2 uint_16
6-94 Terminal 42 Output Max Scale 100.0 % All set-ups TRUE -2 uint_16
6-96 Terminal 42 Output Bus Control 0.0 % All set-ups TRUE -2 uint_16
Parameter Lists VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark 85