13-44 Logic Rule Boolean 3
Array [6]
Option: Function:
[35] Digital input DI27
[36] Digital input DI29
[39] Start command
[40] Drive stopped
[42] Auto reset trip
[50] Comparator 4
[51] Comparator 5
[60] Logic rule 4
[61] Logic rule 5
[70] SL Time-out 3
[71] SL Time-out 4
[72] SL Time-out 5
[73] SL Time-out 6
[74] SL Time-out 7
[83] Broken belt
[100] Firemode
3.9.6 13-5* States
13-51 SL Controller Event
Array [20]
Option: Function:
Select the boolean input (TRUE or
FALSE) to define the Smart Logic
Controller event.
See 13-02 Stop Event for further
descriptions of choices and their
functions.
[0] False
[1] * True
[2] Running
[3] In range
[4] On reference
[7] Out of current range
[8] Below I low
[9] Above I high
[16] Thermal warning
[17] Mains out of range
[18] Reversing
[19] Warning
[20] Alarm (trip)
[21] Alarm (trip lock)
[22] Comparator 0
[23] Comparator 1
[24] Comparator 2
[25] Comparator 3
[26] Logic rule 0
[27] Logic rule 1
[28] Logic rule 2
[29] Logic rule 3
13-51 SL Controller Event
Array [20]
Option: Function:
[30] SL Time-out 0
[31] SL Time-out 1
[32] SL Time-out 2
[33] Digital input DI18
[34] Digital input DI19
[35] Digital input DI27
[36] Digital input DI29
[39] Start command
[40] Drive stopped
[42] Auto reset trip
[50] Comparator 4
[51] Comparator 5
[60] Logic rule 4
[61] Logic rule 5
[70] SL Time-out 3
[71] SL Time-out 4
[72] SL Time-out 5
[73] SL Time-out 6
[74] SL Time-out 7
[83] Broken belt
13-52 SL Controller Action
Array [20]
Option: Function:
Select the action corresponding to the
SLC event. Actions are executed when
the corresponding event (defined in
13-51 SL Controller Event) is evaluated
as true. The following actions are
available for selection:
[0] * Disabled
[1] No action
[2] Select set-up 1
Changes the active set-up (0-10 Active
Set-up) to ‘1’.
[3] Select set-up 2
Changes the active set-up (0-10 Active
Set-up) to ‘2’.
[10] Select preset ref 0 Selects preset reference 0.
[11] Select preset ref 1 Selects preset reference 1.
[12] Select preset ref 2 Selects preset reference 2.
[13] Select preset ref 3 Selects preset reference 3.
[14] Select preset ref 4 Selects preset reference 4.
[15] Select preset ref 5 Selects preset reference 5.
[16] Select preset ref 6 Selects preset reference 6.
[17] Select preset ref 7 Selects preset reference 7. If the active
preset reference is changed, it will
merge with other preset reference
commands coming from either the
digital inputs or via a fieldbus.
Parameters VLT HVAC Basic Drive Programming Guide
56 MG.18.B1.02 - VLT
®