3.14.3 20-9* PI Controller
20-91 PI Anti Windup
Option: Function:
Select Off [0] to continue regulation of an error even
when the output frequency cannot be increased or
decreased. Select On [1] to cease regulation of an error
when the output frequency can no longer be adjusted.
[0] Off
[1] * On
20-93 PI Proportional Gain
Range: Function:
0.01 * [0.0 - 10.0 ] Enter the process controller proportional
gain. Quick control is obtained at high
amplification. However if amplification is too
great, the process may become unstable.
20-94 PI Integral Time
Range: Function:
9999.0 s* [0.1 - 9999.0
s]
Enter the process controller integral time.
Obtain quick control through a short
integral time, though if the integral time
is too short, the process becomes
unstable. An excessively long integral
time disables the integral action.
20-97 PI Feed Forward Factor
Range: Function:
0.0 %* [0.0 - 400.0 %]
Parameters VLT HVAC Basic Drive Programming Guide
68 MG.18.B1.02 - VLT
®
is a registered Danfoss trademark