13-52 SL Controller Action
Array [20]
Option: Function:
[18] Select ramp 1 Selects ramp 1
[19] Select ramp 2 Selects ramp 2
[22] Run Issues a start command to the
frequency converter.
[23] Run reverse Issues a start reverse command to the
frequency converter.
[24] Stop Issues a stop command to the
frequency converter.
[25] Qstop Issues a quick stop command to the
frequency converter.
[26] DC Brake Issues a DC stop command to the
frequency converter.
[27] Coast The frequency converter coasts
immediately. All stop commands
including the coast command stop the
SLC.
[28] Freeze output Freezes the output frequency of the
frequency converter.
[29] Start timer 0
Starts timer 0, see 13-20 SL Controller
Timer for further description.
[30] Start timer 1
Starts timer 1, see 13-20 SL Controller
Timer for further description.
[31] Start timer 2
Starts timer 2, see 13-20 SL Controller
Timer for further description.
[32] Set digital out A low Any output with ‘digital output 1’
selected is low (off).
[33] Set digital out B low Any output with ‘digital output 2’
selected is low (off).
[34] Set digital out C low Any output with ‘digital output 3’
selected is low (off).
[35] Set digital out D
low
Any output with ‘digital output 4’
selected is low (off).
[38] Set digital out A
high
Any output with ‘digital output 1’
selected is high (closed).
[39] Set digital out B
high
Any output with ‘digital output 2’
selected is high (closed).
[40] Set digital out C
high
Any output with ‘digital output 3’
selected is high (closed).
[41] Set digital out D
high
Any output with ‘digital output 4’
selected is high (closed).
[60] Reset Counter A Resets Counter A to zero.
[61] Reset Counter B Resets Counter B to zero.
[70] Start timer 3
Starts timer 3, see 13-20 SL Controller
Timer for further description.
13-52 SL Controller Action
Array [20]
Option: Function:
[71] Start timer 4
Starts timer 4, see 13-20 SL Controller
Timer for further description.
[72] Start timer 5
Starts timer 5, see 13-20 SL Controller
Timer for further description.
[73] Start timer 6
Starts timer 6, see 13-20 SL Controller
Timer for further description.
[74] Start timer 7
Starts timer 7, see 13-20 SL Controller
Timer for further description.
[100] ResetAlarm
Parameters VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark 57
3
3