13-01 Start Event
Option: Function:
[25] Comparator 3 Use the result of comparator 3 in the
logic rule.
[26] Logic rule 0 Use the result of logic rule 0 in the logic
rule.
[27] Logic rule 1 Use the result of logic rule 1 in the logic
rule.
[28] Logic rule 2 Use the result of logic rule 2 in the logic
rule.
[29] Logic rule 3 Use the result of logic rule 3 in the logic
rule.
[33] Digital input DI18 Use the value of DI18 in the logic rule
(High = TRUE).
[34] Digital input DI19 Use the value of DI19 in the logic rule
(High = TRUE).
[35] Digital input DI27 Use the value of DI27 in the logic rule
(High = TRUE).
[36] Digital input DI29 Use the value of DI29 in the logic rule
(High = TRUE).
[39] * Start command This event is TRUE if the frequency
converter is started by any means (either
via digital input, field bus or other).
[40] Drive stopped This event is TRUE if the frequency
converter is stopped or coasted by any
means (either via digital input, fieldbus
or other).
[42] Auto reset trip This event is TRUE if the frequency
converter is tripped (but not trip-locked)
and an Automatic Reset is issued.
[50] Comparator 4 Use the result of comparator 4 in the
logic rule.
[51] Comparator 5 Use the result of comparator 5 in the
logic rule.
[60] Logic rule 4 Use the result of logic rule 4 in the logic
rule.
[61] Logic rule 5 Use the result of logic rule 5 in the logic
rule.
[83] Broken belt A broken belt condition has been
detected. This function must be enabled
in 22-60 Broken Belt Function.
13-02 Stop Event
Option: Function:
Select the condition (TRUE or FALSE)
which will deactivate the Smart Logic
Controller.
[0] False Enters the fixed value of FALSE in the
logic rule.
13-02 Stop Event
Option: Function:
[1] True Enters the fixed value TRUE in the logic
rule.
[2] Running
See 13-01 Start Event for further
description.
[3] In range
See 13-01 Start Event for further
description.
[4] On reference
See 13-01 Start Event for further
description.
[7] Out of current
range
See 13-01 Start Event for further
description.
[8] Below I low
See 13-01 Start Event for further
description.
[9] Above I high
See 13-01 Start Event for further
description.
[16] Thermal warning
See 13-01 Start Event for further
description.
[17] Mains out of range
See 13-01 Start Event for further
description.
[18] Reversing
See 13-01 Start Event for further
description.
[19] Warning
See 13-01 Start Event for further
description.
[20] Alarm (trip)
See 13-01 Start Event for further
description.
[21] Alarm (trip lock)
See 13-01 Start Event for further
description.
[22] Comparator 0 Use the result of comparator 0 in the
logic rule.
[23] Comparator 1 Use the result of comparator 1 in the
logic rule.
[24] Comparator 2 Use the result of comparator 2 in the
logic rule.
[25] Comparator 3 Use the result of comparator 3 in the
logic rule.
[26] Logic rule 0 Use the result of logic rule 0 in the logic
rule.
[27] Logic rule 1 Use the result of logic rule 1 in the logic
rule.
[28] Logic rule 2 Use the result of logic rule 2 in the logic
rule.
[29] Logic rule 3 Use the result of logic rule 3 in the logic
rule.
[30] SL Time-out 0 Use the result of timer 0 in the logic rule.
[31] SL Time-out 1 Use the result of timer 1 in the logic rule.
[32] SL Time-out 2 Use the result of timer 2 in the logic rule.
Parameters VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark 51