3.11 Main Menu - Drive Information - Group
15
Parameter group containing frequency converter
information such as operating data, hardware configuration
and software versions.
3.11.1 15-0* Operating Data
15-00 Operating Hours
Range: Function:
0 h* [0.0 - 2.147483647E9
h]
View how many hours the
frequency converter has run. The
value is saved when the frequency
converter is turned off.
15-01 Running Hours
Range: Function:
0 h* [0.0 - 2.147483647E9
h]
View how many hours the motor has
run. Reset the counter in 15-07 Reset
Running Hours Counter. The value is
saved when the frequency converter
is turned off.
15-02 kWh Counter
Range: Function:
0 kWh* [0.0 - 65535
kWh]
View the output power of the frequency
converter in kWh as a mean value over
one hour. Reset the counter in 15-06 Reset
kWh Counter.
15-03 Power Up's
Range: Function:
0 * [0.0 - 2147483647 ] View the number of times the frequency
converter has been powered up.
15-04 Over Temp's
Range: Function:
0 * [0.0 - 65535 ] View the number of frequency converter
temperature faults which have occurred.
15-05 Over Volt's
Range: Function:
0 * [0.0 - 65535 ] View the number of frequency converter
overvoltages which have occurred.
15-06 Reset kWh Counter
Option: Function:
[0] * Do not reset
[1] Reset counter
Select Reset [1] and press [OK] to reset the
kWh counter to zero (see 15-02 kWh Counter).
NOTE
The reset is carried out by pressing [OK].
15-07 Reset Running Hours Counter
Option: Function:
[0] * Do not reset
[1] Reset counter
Select Reset counter [1] and press [OK] to reset
Running Hours counter (15-01 Running Hours)
and to zero (see also 15-01 Running Hours).
3.11.2 15-3* Alarm Log
Parameters in this group are array parameters, where up to
10 fault logs can be viewed. [0] is the most recent logged
data, and [9] the oldest. Error codes, values, and time stamp
can be viewed for all logged data.
15-30 Alarm Log: Error Code
Range: Function:
0 * [0.0 - 255 ] View the error code and look up its meaning in
the Troubleshooting chapter.
15-31 Alarm Log: Value
Range: Function:
0 * [-32767 - 32767] View a description of the error. This
parameter is used in combination with
alarm 38 Internal Fault.
3.11.3 15-4* Drive Identification
Parameters containing read only information about the
hardware and software configuration of the frequency
converter.
15-40 FC Type
Range: Function:
0 * [0 - 0 ] View the FC type. The read-out is identical to the
frequency converter series power field of the type
code definition, characters 1-6.
15-41 Power Section
Range: Function:
0 * [0 - 0 ] View the FC type. The read-out is identical to the
frequency converter series power field of the type
code definition, characters 7-10.
15-42 Voltage
Range: Function:
0 * [0 - 0 ] View the FC type. The read-out is identical to the
frequency converter series power field of the type
code definition, characters 11-12.
Parameters VLT HVAC Basic Drive Programming Guide
MG.18.B1.02 - VLT
®
is a registered Danfoss trademark 61
3
3