Solar-Log1000: Configuration at the unit
Configuring the inverter data (Basic/Inverter)
Solar-Log
1000/500/200
Installation 225 of 268
Entering a pulse factor (only or S0 meter)
In the standard setting, Solar-Log™ sends 1000 pulses/kWh over the S0 out-
put. The pulse factor of the Solar-Log™ dRS-485 communications package
must be adapted to the pulse factor of the connected meter.
Note
The pulse factor of Solar-Log
1000
and of the S0 meter must be set to the same
value.
Procedure
In order to change the pulse factor:
1 Touch the number box beside Pulse factor
The virtual keyboard is opened.
2 Enter the desired pulse factor and confirm with OK
3 Touch Save, then Next to go to the next dialogue.
Setting the S0 meter
This subdialog box is available only if a current meter is connected to Solar-
Log
1000
and has been selected.
Dialogue boxes
The S0 meter is flexible and can be set in 3 modes:
– in Inverter mode for inverters with data protocols that are not supported
– as Overall yield meter to count the total output from the entire system
– as Consumption meter to calculate the system's own consumption rate
Connect. module power
A value for the connected module power is needed in inverter mode, in or-
der to make power comparisons between the different inverters and offset
them against each other.
Module field (1-9)
In the module field, the same types of strings are placed together for sys-
tem monitoring and to be monitored together. For a roof with equal mod-
ules, which have the same alignment and the same angle of inclination on
the roof, all strings are assigned to module field “1”. If there are other in-
verters connected, which are operating with a different roof alignment,
these strings are given the module field number “2”. etc.