Connecting the inverters
Diehl AKO with RS485 interface
64 of 268 Solar-Log
1000/500/200
Installation
4.24 Diehl AKO with RS485 interface
Overview
Interface integrated
Where to connect: RJ45 socket on the bottom of the inverter
2 pin wiring
Communication address does not have to be allocated.

Note
The order in which the inverters are displayed in the Solar-Log™ after detection
is random. We strongly recommend that you change the order of the inverters
immediately after detection at startup, in the Configuration/Basic/Inverter
dialogue box (Page 162).
The inverters can be identified using the displayed serial number.
Work steps
Switch off the inverters and the SolarLog™; Page 17
Connect inverters to the Solar-Log
Connect the inverters to each other
Connecting inverters to the Solar-Log
The wiring is done using the
ready-made data cable (optional extra; not supplied)
or
your own fabricated cable connection with RJ45 plug and terminal
block connector ( Page 15)
Procedure
1 If you are fabricating the cable yourself, connect the wires as shown in the
following diagram:
Solar-Log™ terminal block connector
RJ45 inverter
Terminal
Pin
1
PIN 6 (A)
4
PIN 3 (B)
2 Insert the RJ45 plug into the RJ45 socket on the inverter.
3 If only one inverter is to be connected terminate this in accordance with the
inverter instructions.
4 Insert the terminal block connector into the Solar-Log™ RS485 socket.